The signal normalizer is designed to amplify the signal from bridge strain gauge sensors. It can be located in close proximity to the sensor in the production area. The signal normalizer includes a power amplifier-former for the strain gauge sensor power supply and a differential amplifier for the strain gauge signal. It has galvanic isolation between the input, output, and power supply – 1.5 kV.
Parameters | Values |
---|---|
Number of connected sensors | 1, 2, 3, 4 |
Input signal, mV | 0...30 |
Output signal, V | 0 – 10 |
Amplification factor | 330, 495, 660, 990 |
Sensor power supply voltage, V | 10 |
Power supply voltage of the normalizer, V | 24 |
Protection class | IP65 |